PVC, PVC-FR or Halogen-Free? Choosing the Right Cable for Your Plant

PVC is not halogen-free. Polyvinyl chloride contains chlorine, which is a halogen. Flame-retardant PVC-FR also contains halogens. Material, fire performance and installation conditions therefore need separate checks when selecting a cable.

Comparing PVC, PVC-FR and halogen-free versions

VersionHalogen-free?What to check
PVCNoTemperature range, mechanical loads and permitted installation conditions
PVC-FRNoFlame-retardant version; check the fire tests specified for the cable
Halogen-freeAccording to the stated test requirementsCheck smoke emission and flame propagation separately

PVC for standard applications

PVC is used for insulation and sheaths. Suitability for a particular installation also depends on the cable construction. Check temperature limits, movement and the stated conditions for indoor or outdoor use.

Our range includes PVC versions among control cables and power cables.

PVC-FR: flame-retardant, but not halogen-free

FR stands for flame retardant. The PVC-FR compound is formulated for this property. Check which requirements the finished cable meets. A bundle flame test to IEC 60332-3-24 describes behaviour under defined conditions; it does not guarantee self-extinguishing behaviour in every real fire.

PVC-FR can still release corrosive, halogen-containing gases in a fire. FR does not establish halogen-free or low-smoke performance.

Examples in our installation cable range include JE-Y(St)Y-FR with solid conductors and JE-LIYCY-FR with stranded conductors. Check the data sheet for the selected version.

Halogen-free cables: check each fire property

LSZH means Low Smoke Zero Halogen. The relevant test evidence must be stated for the cable.

Halogen-free materials limit the release of halogen acid gases under the specified test requirements. This does not mean that a fire produces no toxic gases. Flame retardance and low smoke emission need separate evidence:

  • IEC 60754-1: halogen acid gas content
  • IEC 60754-2: acidity and conductivity of combustion gases
  • IEC 61034-2: smoke density under defined test conditions
  • IEC 60332-1-2: vertical flame propagation on a single insulated wire or cable
  • IEC 60332-3-24: vertical flame propagation on bunched cables, category C

Compare the project’s requirements with the evidence for the exact cable type. Halogen-free installation cable versions include JE-H(St)H and JE-LIHCH.

Halogen-free types in our range

For plants in power-plant and industrial environments we supply halogen-free versions in several product areas. The details are taken from the respective datasheets:

Product areaTypeDatasheet statement
Installation cablesJE-H(St)H, JE-HCH, JE-LIHCHhalogen-free and flame-resistant, for increased fire protection requirements
Control cablesHSLH-OZ/JZhalogen-free and flame-retardant, for indoor use, largely oil-resistant
Power cables 0.6/1 kVN2XH-O/J, N2XCHlow-smoke, zero-halogen (LSZH), flame-retardant
Data cablesXLAN 1000 S/FTP FRNChalogen-free FRNC sheath, Category 7

The fire tests a cable actually passes are listed in its datasheet.

Can halogen-free cables be buried?

Halogen-free status does not establish suitability for direct burial. Cable construction and the stated installation conditions determine where the cable can be used. For the JE indoor types mentioned above, check the moisture and installation restrictions in the individual data sheet. A protective conduit does not replace this check.

For other service conditions, see the special cable range and the application details for each version.

Selecting a cable for your plant

Specify the location, installation method, operating voltage and required fire tests. Add conductor count, cross-section and length. Our data sheet search helps compare versions.

Send us your project requirements for help selecting a cable type. Our quality management has been certified to ISO 9001 since 1996.

Types mentioned in this article

Open the datasheet, or collect them straight into one inquiry.

JE-H(St)H Bd Si mtp B2ca / Cca / Dcaacc. to DIN VDE 0815
JE-HCH Bd Si mtp B2ca / Cca / Dcaacc. to DIN VDE 0815
JE-LIHCH Bd Si mtp Eca/Dcaacc. to DIN VDE 0815
HSLH-OZ/JZacc. to DIN EN 50267/IEC 60754
N2XH-O/J 0.6/1kVacc. to VDE 0276-604
N2XCH 0.6/1kVacc. to VDE 0276-604
← All articles
Inquiry · personal and project-based

Send us your cable requirement.

Type, cross-section, quantity, delivery location: we review availability, price and lead time according to your enquiry. Personally and without unnecessary detours.

Request a quote info@tk-kabel.de
T. +49 (0) 7151 / 60 68 70

Inquiry list

Paste your bill of materials or collect types from the datasheet tables. We review every line and reply with availability, price and lead time.

From Excel, e-mail or PDF, one item per line. Or drop a file here.

The file is read in your browser and is not uploaded.

Items 0

No items yet. Paste your list above, or use “+ Inquiry” in the datasheet tables.

    Try LIYCY, halogen-free, drum, CPR or paste several lines.

    Enter opens · Esc closes

    Request a call back

    Leave your number and we will call you during office hours, Mon-Fri 9:00 a.m.-5:00 p.m. No form to fill in.

    When suits you?

    We only use your number for this call back. Details in our privacy policy.