PVC is not halogen-free. Polyvinyl chloride contains chlorine, which is a halogen. Flame-retardant PVC-FR also contains halogens. Material, fire performance and installation conditions therefore need separate checks when selecting a cable.
Comparing PVC, PVC-FR and halogen-free versions
| Version | Halogen-free? | What to check |
|---|---|---|
| PVC | No | Temperature range, mechanical loads and permitted installation conditions |
| PVC-FR | No | Flame-retardant version; check the fire tests specified for the cable |
| Halogen-free | According to the stated test requirements | Check smoke emission and flame propagation separately |
PVC for standard applications
PVC is used for insulation and sheaths. Suitability for a particular installation also depends on the cable construction. Check temperature limits, movement and the stated conditions for indoor or outdoor use.
Our range includes PVC versions among control cables and power cables.
PVC-FR: flame-retardant, but not halogen-free
FR stands for flame retardant. The PVC-FR compound is formulated for this property. Check which requirements the finished cable meets. A bundle flame test to IEC 60332-3-24 describes behaviour under defined conditions; it does not guarantee self-extinguishing behaviour in every real fire.
PVC-FR can still release corrosive, halogen-containing gases in a fire. FR does not establish halogen-free or low-smoke performance.
Examples in our installation cable range include JE-Y(St)Y-FR with solid conductors and JE-LIYCY-FR with stranded conductors. Check the data sheet for the selected version.
Halogen-free cables: check each fire property
LSZH means Low Smoke Zero Halogen. The relevant test evidence must be stated for the cable.
Halogen-free materials limit the release of halogen acid gases under the specified test requirements. This does not mean that a fire produces no toxic gases. Flame retardance and low smoke emission need separate evidence:
- IEC 60754-1: halogen acid gas content
- IEC 60754-2: acidity and conductivity of combustion gases
- IEC 61034-2: smoke density under defined test conditions
- IEC 60332-1-2: vertical flame propagation on a single insulated wire or cable
- IEC 60332-3-24: vertical flame propagation on bunched cables, category C
Compare the project’s requirements with the evidence for the exact cable type. Halogen-free installation cable versions include JE-H(St)H and JE-LIHCH.
Halogen-free types in our range
For plants in power-plant and industrial environments we supply halogen-free versions in several product areas. The details are taken from the respective datasheets:
| Product area | Type | Datasheet statement |
|---|---|---|
| Installation cables | JE-H(St)H, JE-HCH, JE-LIHCH | halogen-free and flame-resistant, for increased fire protection requirements |
| Control cables | HSLH-OZ/JZ | halogen-free and flame-retardant, for indoor use, largely oil-resistant |
| Power cables 0.6/1 kV | N2XH-O/J, N2XCH | low-smoke, zero-halogen (LSZH), flame-retardant |
| Data cables | XLAN 1000 S/FTP FRNC | halogen-free FRNC sheath, Category 7 |
The fire tests a cable actually passes are listed in its datasheet.
Can halogen-free cables be buried?
Halogen-free status does not establish suitability for direct burial. Cable construction and the stated installation conditions determine where the cable can be used. For the JE indoor types mentioned above, check the moisture and installation restrictions in the individual data sheet. A protective conduit does not replace this check.
For other service conditions, see the special cable range and the application details for each version.
Selecting a cable for your plant
Specify the location, installation method, operating voltage and required fire tests. Add conductor count, cross-section and length. Our data sheet search helps compare versions.