Power Cables
This overview contains power cables rated 0.6/1 kV for energy distribution in industrial plants, power stations and switchgear installations. The range includes PVC or XLPE core insulation, PVC or halogen-free sheaths, and versions with a concentric copper conductor.
Select a power cable by construction
| Requirement | Example and characteristics |
|---|---|
| PVC-insulated power distribution cable | NYY-O/J: copper conductors, PVC core insulation and PVC sheath. The datasheet lists installation in soil, water, indoors and outdoors, among other locations. |
| PVC insulation with a concentric copper conductor | NYCY or NYCWY. NYCWY has a wave-shaped concentric conductor in a ceander arrangement. |
| XLPE insulation with a PVC sheath | N2XY-O/J: for indoor and outdoor use and burial where increased mechanical protection is not required. N2XCY adds a concentric copper conductor. |
| Halogen-free, low-smoke version | N2XH-O/J: XLPE core insulation and a halogen-free sheath. N2XCH also has a concentric copper conductor. |
Check installation conditions
N2XH and N2XCH are intended for installation indoors and in concrete. Outdoors, they must be protected from sunlight; direct installation in soil or water is excluded. These restrictions distinguish them from the NYY and N2XY versions specified for the relevant installation conditions.
The full table contains further versions, including NYY-OZ/JZ, NYYSYö-FR and N2XY-FR. Construction, dimensions and installation details are provided in the individual datasheets.
Enquire about a power cable
Please specify the type, number of cores, cross-section, required conductor shape, length and installation location. If a concentric conductor is required, include its cross-section. Add the required reaction-to-fire class, delivery date and any project specifications.
Use the quick enquiry form below the table. If the cable version has not yet been selected, describe the application and installation conditions.
| Type code | Characteristics | Standard | Datasheet |
|---|---|---|---|
| NYY-O/J 0.6/1 kV | outdoor / indoor / direct burialPVC | acc. to VDE 0276-603 | |
| NYY-OZ/JZ 0.6/1 kV | outdoor / indoor / direct burialPVC | acc. to VDE 0276-603 | |
| NYCY 0.6/1 kV | outdoor / indoor / direct burialPVCscreened | acc. to VDE 0276 | |
| NYCWY 0.6/1 kV | outdoor / indoor / direct burialPVCconcentric | acc. to VDE 0276-603 | |
| NYYSYö-FR-O/J 0.6/1 kV | outdoor / indoor / direct burialPVC-FRoil-resistant | based on VDE 0276-603 | |
| 2XY-O/J (R2V) 0.6/1kV | outdoor / indoorXLPEPVC | acc. to NF C 32-321, IEC 60502 | |
| N2XY-O/J 0.6/1kV | outdoor / indoor / direct burialXLPEPVC | acc. to VDE 0276-603 | |
| N2XCY 0.6/1kV | outdoor / indoor / direct burialXLPEPVCscreened | acc. to VDE 0276-603 | |
| N2XY-FR-O/J 0.6/1kV | outdoor / indoor / direct burialXLPEPVC-FR | acc. to VDE 0276-603 | |
| N2XH-O/J 0.6/1kV | indoor / protected outdoorhalogen-freeXLPE | acc. to VDE 0276-604 | |
| N2XCH 0.6/1kV | indoor / protected outdoorhalogen-freeXLPEscreened | acc. to VDE 0276-604 |
Quick inquiry
Personal, technical advice for your inquiry.
Send us your cable requirement.
Type, cross-section, quantity, delivery location: we review availability, price and lead time according to your enquiry. Personally and without unnecessary detours.