Skip to content
Power Cables · acc. to VDE 0276-603

NYCWY 0.6/1 kV

What the code means
N
VDE standard
Y
PVC
CW
concentric copper conductor, wave-form
Y
PVC
0.6/1 kV
0.6/1 kV
Decode another code

Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes, street lighting as well as a control cable for the transmission of control impulses and test data. Anywhere where increased electrical and also mechanical protection is required. These cables are installed outdoors, underground, in water, in concrete, indoors and in cable ducts.

outdoor / indoor / direct burialPVCconcentric
Request this type Datasheet (PDF)
Key data
Standard
acc. to VDE 0276-603
Nominal voltage
0.6/1 kV
Temperature range during installation
-5°C to +50°C
Temperature range stationary
-40°C to +70°C
Category
Power Cables
Datasheet
Download PDF
Type
NYCWY 0.6/1 kV
Shown
4 x 10/10 RE
Core marking
DIN VDE 0293
Schematic, not to scale.

Construction

  1. 1Conductor copper, bare, single-wire or multi-wire
  2. 2Core insulation PVC DIV 4
  3. 3Outer sheath PVC DMV 5 flame retardant; colour: black
  • Core identification colours acc. to DIN VDE 0293
  • Core stranding cores twisted to layers
  • Concentric conductor copper wires, wave form (ceander), with cu- tape counter helix

Choose your construction

All constructions from the datasheet. Select a row and enter a length to see weight, copper and bending radius.

37 constructions
NYCWY 0.6/1 kV: Dimensions, approximate diameter, cable weight and copper index
DimensionØ mmkg/kmCu index kg/km
241,7611,472
32.64,0673,634
19.4610312
20.4840489
25.11,340763
30.32,0451,243
19.4750408
21.41,050643
25.51,600902
27.61,7001,190
28.72,3001,723
32.82,9002,410
37.84,0003,296
40.85,0004,236
456,0005,100
507,5006,383
5710,0008,242
25.51,6001,003
25.71,8501,402
28.72,4002,000
33.83,3002,796
37.84,5003,791
41.85,5004,786
466,7505,970
20.4870504
23.41,250796
23.41,250796
27.61,8001,142
28.62,0501,526
32.82,7002,203
36.83,7503,082
43.95,0004,208
476,3005,388
517,6006,540
569,3008,159
6311,60010,546
69.615,33113,170

Need a different construction?

Ask us to check a variant. We confirm screening, dimensions, voltage and installation conditions together before proposing an alternative.

Quick inquiry - NYCWY 0.6/1 kV

Personal, technical advice for your inquiry.

When you submit the form, we process your information to handle your inquiry. Details can be found in our privacy policy.

Inquiry · personal and project-based

Send us your cable requirement.

Type, cross-section, quantity, delivery location: we review availability, price and lead time according to your enquiry. Personally and without unnecessary detours.

Request a quote info@tk-kabel.de
T. +49 (0) 7151 / 60 68 70

Inquiry list

Paste your bill of materials or collect types from the datasheet tables. We review every line and reply with availability, price and lead time.

From Excel, e-mail or PDF, one item per line. Or drop a file here.

The file is read in your browser and is not uploaded.

Items 0

No items yet. Paste your list above, or use “+ Inquiry” in the datasheet tables.

    Try LIYCY, halogen-free, drum, CPR or paste several lines.

    Enter opens · Esc closes

    Request a call back

    Leave your number and we will call you during office hours, Mon-Fri 9:00 a.m.-5:00 p.m. No form to fill in.

    When suits you?

    We only use your number for this call back. Details in our privacy policy.