Skip Navigation View Sitemap

Outdoor cables (PVC)

AJ-Y(St)YDYT-FR Bd Si Cu3,5

AJ-Y(St)YDYT-FR Bd Si Cu3,5 in resemblance to DIN VDE 0815
Application

For information transmission in dry and moist production sites, in and under plaster, as well as outdoors for fixed installation. Not approved for power installation, but appropriate for underground installation.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: PVC
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: PVC
  • Weir / Screen: cross section 3.5 mm²; surrounded with 7 bare copper wires (Ø 0.8 mm); lapping with plastic foil
  • Outer sheath: PVC-FR; termite protected; colour: black RAL 9005
Behaviour under fire conditions
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Low smoke and fume

A-Y(St)YSYT-FR Bd Si

A-Y(St)YSYT-FR Bd Si
in resemblance to DIN VDE 0815
Application

For information transmission in dry and moist production sites, in and under plaster, as well as outdoors for fixed installation. Not approved for power installation, but appropriate for underground installation.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: PVC
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: PVC
  • Armouring: galvanized steel wire braid (Ø 0.24 mm); optical coverage approx. 80 %
  • Outer sheath: PVC-FR; termite protected; colour: black RAL 9005
Behaviour under fire conditions
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Low smoke and fume

A-Y(St)YDSYT-FR Bd Si

A-Y(St)YDSYT-FR Bd Si
in resemblance to DIN VDE 0815
Application

For information transmission in dry and moist production sites, in and under plaster, as well as outdoors for fixed installation. Not approved for power installation, but appropriate for underground installation.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: PVC
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: PVC
  • Weir / Rodent protection: galvanized steel shield (Ø 0.8 mm); optical coverage > 85%
  • Outer sheath: PVC-FR; termite protected; colour: black RAL 9005
Behaviour under fire conditions
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Low smoke and fume

A-LIY(St)YDSYT-FR PimF Bd Si

A-LIY(St)YDSYT-FR PimF Bd Si
in resemblance to DIN VDE 0815
Application

For information transmission in dry and moist production sites, in and under plaster, as well as outdoors for fixed installation. Not approved for power installation, but appropriate for underground installation.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: PVC
  • Shielded pairs: each pair one layer plastic tape; drain wire: tinned copper strand 7 x 0.16 mm; one layer plastic laminated aluminium foil
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: PVC
  • Weir / Rodent protection: galvanized steel shield (Ø 0.8 mm); optical coverage > 85%
  • Outer sheath: PVC-FR; termite protected; colour: black RAL 9005
Behaviour under fire conditions
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Low smoke and fume
Back to top