SPECIAL CABLES ➤ INDOOR CABLE ➤ HALOGEN-FREE, TERMITE PROTECTED, WATER RESISTANT, RODENT PROTECTION

JE-LIHCHSHSOT Bd Si mtp
in resemblance to DIN VDE 0815 

JE-LIHCHSHSOT Bd Si mtp

APPLICATION

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Termite resistant and rodent proof. Appropriate for water installation.

CONSTRUCTION

Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)

Core insulation: halogen-free compound

Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad

Lapping: plastic foil

Screen: tinned copper wire braid (Ø 0.2 mm)

Sheath: halogen free compound

Armouring: galvanized steel wire braid (Ø 0.24 mm); optical coverage > 60 %

Outer sheath: layer 1: halogen-free compound layer 2: special halogen-free compound; termite protected; colour: pebble grey RAL 7032 or blue RAL 5015

BEHAVIOUR UNDER FIRE CONDITIONS

Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267

Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2

Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24

Smoke density: IEC 61034, DIN EN 61034