Conductor: copper, bare, single-wire or multi-wire
Core insulation: XLPE (cross-linked polyethylene)
Core identification: colours acc. to DIN VDE 0293
Core stranding: cores twisted to layers
Outer sheath: halogen-free compound; colour: black
BEHAVIOUR UNDER FIRE CONDITIONS
Zero halogen, non corrosive gases: IEC 60754, DIN EN 50267
Fire retardant: IEC 60332-3-24 cat. C, DIN EN 50266-2-4
Smoke density: IEC 61034, DIN EN 61034
N2XCH 0.6/1kV
N2XCH 0.6/1kV
acc. to VDE 0276-604
APPLICATION
Low-smoke, zero-halogen, flame retardant power cable. For fixed indoor and outdoor installation. Can be placed in concrete. Not for direct burial in earth or application in water.