CONTROL CABLES ➤ FEP

LI6YC6Y (4+2) x 0.75 GY/BU
 

LI6YC6Y (4+2) x 0.75 GY/BU

APPLICATION

• in heat-appliances and fire resistant installations
• wiring of controls and computers with high transfer-speed
• plants in industrial atmosphere
• in the chemical industry

CONSTRUCTION

Conductor: tinned copper strand; 24 x 0.2 mm = 0.75 mm²

Core insulation: FEP; wall thickness 0.3 mm; Ø 1.75 ± 0.10 mm

Core identification: black, blue, brown, green-yellow;
screened: orange and natural colour

Core screen: 2 cores screened with a tinned copper wire braid (Ø 0.1 mm)

Filler: glass fibre; blind line made from silicone

Lapping: polyester tape

Screen: tinned copper wire braid; optical coverage approx. 85 %

Outer sheath: FEP; colour: grey (GY) or blue (BU)