Skip Navigation View Sitemap

Bus cables

02YS(St)CY

02YS(St)CY
acc. to DIN 19245 T3 and EN 50170 (acc. Profibus specification)
Application

The cable can be used as connecting cable in general machinery construction. It is used as a connection cable between bus segments. Cost-efficient plant and machinery wiring is the great advantage of bus technology. Only the information-related component responds to the signal and processes it. The cable is appropriate for indoor installation.

Application
  • Conductor: copper wire, solid, bare (AWG 22/1)
  • Core insulation: Foam-Skin PE
  • Core identification: red, green
  • Core stranding: 2 cores and 2 filling cores stranded
  • Lapping: plastic foil
  • Screen: Al/PETP compound foil; tinned copper wire braid; optical coverage approx. 80%
  • Outer sheath: PVC; colour: violet RAL 4001

02YS(St)CY2Y

02YS(St)CY2Y
acc. to DIN 19245 T3 and EN 50170 (acc. Profibus specification)
Application

The cable can be used as connecting cable in general machinery construction. It is used as a connection cable between bus segments. Cost-efficient plant and machinery wiring is the great advantage of bus technology. Only the information-related component responds to the signal and processes it. The cable is applicable for indoor and outdoor installation.

Construction
  • Conductor: copper wire, solid, bare (AWG 22/1)
  • Core insulation: Foam-Skin PE
  • Core identification: red, green
  • Core stranding: 2 cores and 2 filling cores stranded
  • Lapping: plastic foil
  • Screen: Al/PETP compound foil; tinned copper wire braid; optical coverage approx. 80%
  • Sheath: PVC; colour: violet RAL 4001
  • Outer sheath: PE; colour: black RAL 9005

02YSY(St)CY-FR

02YSY(St)CY-FR
acc. to DIN 19245 T3 and EN 50170 (acc. Profibus specification)
Application

The cable can be used as connecting cable in general machinery construction. It is used as a connecting cable between bus segments. Cost-efficient plant and machinery wiring is the great advantage of bus technology. Only the information related component responds to the signal and processes it. Together with the appropriate tools and connectors the cable is appropriate for quick-assembly technology.

Construction
  • Conductor: copper wire, solid, bare (AWG 22/1)
  • Core insulation: Foam-Skin PE
  • Core identification: red, green
  • Core stranding: 2 cores stranded
  • Filling sheath: filling compound
  • Lapping: plastic foil
  • Screen: Al/PETP compound foil; tinned copper wire braid; optical coverage approx. 80%
  • Outer sheath: PVC-FR; colour: violet RAL 4001
Behaviour under fire conditions
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Low smoke and fume

02YS(St)CH

02YS(St)CH
acc. to DIN 19245 T3 and EN 50170 (acc. Profibus specification)
Application

The cable can be used as connecting cable in general machinery construction. It is used as a connection cable between bus segments. Cost-efficient plant and machinery wiring is the great advantage of bus technology. Only the information-related component responds to the signal and processes it. The cable is appropriate for indoor installation.

Construction
  • Conductor: copper wire, solid, bare (AWG 22/1)
  • Core insulation: Foam-Skin PE
  • Core stranding: 2 cores and 2 filling cores stranded
  • Lapping: plastic foil
  • Screen: Al/PETP compound foil; tinned copper wire braid; optical coverage approx. 80%
  • Outer sheath: halogen-free compound; colour: violet RAL 4001
Back to top