Outdoor cables (halogenfree)

A-H(St)HCH Bd Si mtp Fca

A-H(St)HCH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Screen: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

AJ-H(St)HDH Bd Si Cu3,5 mtp Fca

AJ-H(St)HDH Bd Si Cu3,5 mtp Fca
in resemblance to DIN VDE 0815
Anwendung

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Application
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Weir / Screen: cross section 3.5 mm²; surrounded with 7 bare copper wires (Ø 0.08 mm); lapping with plastic foil
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-H(St)HSH Bd Si mtp Fca

A-H(St)HSH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Application
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Armouring: galvanized steel wire braid (Ø 0.24 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-H(St)HDSH Bd Si mtp Fca

A-H(St)HDSH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Weir / Rodent protection: galvanized steel shield; (Ø 0.9 mm or 1.4 mm); optical coverage approx. 80%
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

AJ-HCHDH Bd Si Cu16 mtp Fca

AJ-HCHDH Bd Si Cu16 mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm)
  • Sheath: halogen-free compound
  • Weir / Screen: cross section 16 mm²; surrounded with 16 bare copper wires (Ø 1.13 mm); lapping with plastic foil
  • Outer sheath: PE L/MD; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

AJ-HCHD2Y Bd Si Cu16 mtp Fca

AJ-HCHD2Y Bd Si Cu16 mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Application
  • Conductor: copper, solid, bare (Ø 0.8 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm)
  • Sheath: halogen-free compound
  • Weir / Screen: cross section 16 mm²; surrounded with 16 bare copper wires (Ø 1.13 mm); lapping with plastic foil
  • Outer sheath: PE L/MD; colour: black RAL 9005

A-LIH(St)HCH Bd Si mtp Fca

A-LIH(St)HCH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Application
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Screen: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-LIH(St)HDSH Bd Si mtp Fca

A-LIH(St)HDSH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Shield: tinned drain wire (Ø 0.8 mm); plastic-laminated aluminium foil
  • Sheath: halogen-free compound
  • Weir / Rodent protection: galvanized steel shield (Ø 0.9 mm or 1.4mm); optical coverage approx. 80%
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-LIHCH Bd Si mtp Fca

A-LIHCH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-LIHCHCH Bd Si mtp Fca

A-LIHCHCH Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen 1: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Sheath: halogen-free compound
  • Screen 2: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034

A-LIHCHCH PimF Bd Si mtp Fca

A-LIHCHCH PimF Bd Si mtp Fca
in resemblance to DIN VDE 0815
Application

This halogen-free, flame-resistant cable is used where increased fire protection of persons, material goods and buildings is required. It serves for signal transmission in communication systems with fixed installation. Not approved for power installation. Due to water absorption the cable should only be laid directly in earth or water if a protective conduit is used.

Construction
  • Conductor: copper strand, bare; 7 x 0.3 mm = 0.5 mm² (Ø 0.9 mm)
  • Core insulation: halogen-free compound
  • Shielded pairs: each pair one layer plastic tape; drain wire: tinned copper strand 7 x 0.16 mm; one layer plastic laminated aluminium foil
  • Core stranding: 2 cores to pair, 4 pairs to unit, units in layers; 2 x 2 as star quad
  • Lapping: plastic foil
  • Screen 1: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Sheath: halogen-free compound
  • Screen 2: tinned copper wire braid (Ø 0.2 mm); optical coverage approx. 80 %
  • Outer sheath: halogen-free compound; colour: black RAL 9005
Behaviour under fire conditions
  • Zero halogen, non corrosive gases: IEC 60754-2, DIN EN 50267
  • Flame retardant: IEC 60332-1-2, DIN EN 60332-1-2
  • Fire retardant: IEC 60332-3-22 / 24, DIN EN 60332-3-22 / 24
  • Smoke density: IEC 61034, DIN EN 61034